Depending on the amount of data to process, file generation may take longer.

If it takes too long to generate, you can limit the data by, for example, reducing the range of years.

Article

Download BibTeX

Title

Localisation of partial discharges sources using acoustic transducers arrays

Authors

[ 1 ] Instytut Elektroenergetyki, Wydział Elektryczny, Politechnika Poznańska | [ P ] employee

Year of publication

2014

Published in

Computer Applications in Electrical Engineering

Journal year: 2014 | Journal volume: vol. 12

Article type

scientific article

Publication language

english

Keywords
EN
  • partial discharge
  • signal source localisation
  • transducer array
  • direction of arrival (DOA) estimation
  • MUSIC
Abstract

EN This paper concerns the issue of the partial discharge (PD) sources location using acoustic emission transducer arrays technique and the high resolution direction of arrival estimation technology. In addition to the theoretical assumptions of both techniques, the simulation result, in which an uniform linear array (ULA) was used for registration of the acoustic emission signals generated by defects in power transformer insulation system were shown. To estimate the direction of arrival (DOA) of acoustic signals, that propagate from the discharge-generating defect to the transducer array installed on transformer tank, Multiple Signal Classification (MUSIC) algorithm was chosen. With the ability to locate multisource discharges (even at very low signal-to-noise ratio – SNR), the adopted solution has advantages over conventional techniques.

Pages (from - to)

237 - 245

Ministry points / journal

6

This website uses cookies to remember the authenticated session of the user. For more information, read about Cookies and Privacy Policy.