Depending on the amount of data to process, file generation may take longer.

If it takes too long to generate, you can limit the data by, for example, reducing the range of years.

Article

Download BibTeX

Title

Inaccuracy of short-term light flicker Pst indicator measuring with a flickermeter

Authors

[ 1 ] Instytut Elektrotechniki i Elektroniki Przemysłowej, Wydział Elektryczny, Politechnika Poznańska | [ P ] employee

Year of publication

2012

Published in

IEEE Transactions on Power Delivery

Journal year: 2012 | Journal volume: vol. 27 | Journal number: no. 2

Article type

scientific article

Publication language

english

Keywords
EN
  • flickermeter
  • inaccuracy
  • Pst indicator
Abstract

EN This paper provides an analysis of the short-term light flicker indicator measuring inaccuracy. Due to the complexity of a flickermeter's signal path, a full analysis is practically impossible. With the use of a standard functional diagram and flickermeter's model equations, it has been possible to describe the most important reasons behind the measurement inaccuracy: reference value restoration inaccuracy, the discrepancy between the acquired filters' amplitude responses, and standard filter characteristics, the attenuation of the maximum signal values transmitted through internal filters cascade, and some difficulties with flicker-level statistical evaluation. With the help of the amplitude response, suggestions on sample rate selection for internal signals have been given.

Pages (from - to)

842 - 848

DOI

10.1109/TPWRD.2011.2181962

URL

https://ieeexplore.ieee.org/document/6151205

Impact Factor

1,519

This website uses cookies to remember the authenticated session of the user. For more information, read about Cookies and Privacy Policy.