Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation

Authors

[ 1 ] Instytut Elektroenergetyki, Wydział Elektryczny, Politechnika Poznańska | [ P ] employee

Year of publication

2006

Published in

IEEE Transactions on Power Delivery

Journal year: 2006 | Journal volume: vol. 21 | Journal number: no. 3

Article type

scientific article

Publication language

english

Keywords
EN
  • conductivity
  • dielectric frequency response
  • modeling
  • moisture content
  • oil-paper insulation
Abstract

EN Knowledge about moisture content in oil impregnated paper insulation is essential when estimating remaining lifetime of power transformers. Direct evaluation of moisture content is rarely possible due to inaccessibility of the internal insulation system in transformers. Therefore, various indirect estimation techniques are utilized. Frequency domain spectroscopy (FDS) measurements of transformer insulation belong to this group. To perform high quality interpretation of results of FDS measurements a good knowledge on dielectric responses in oil impregnated pressboard and paper is required, especially as it refers to their variation with water content and temperature. The aim of this paper is to provide an open access to the frequency domain spectra of oil impregnated paper and pressboard samples, which can then be used in modeling of the results of diagnostic measurements in power transformers.

Pages (from - to)

1309 - 1317

DOI

10.1109/TPWRD.2006.877632

URL

https://ieeexplore.ieee.org/document/1645170

Impact Factor

0,496

This website uses cookies to remember the authenticated session of the user. For more information, read about Cookies and Privacy Policy.