Depending on the amount of data to process, file generation may take longer.

If it takes too long to generate, you can limit the data by, for example, reducing the range of years.

Article

Download file Download BibTeX

Title

Zasady poprawnego wykonywania pomiarów transformatorów energetycznych przy użyciu metody SFRA

Authors

[ 1 ] Wydział Elektryczny, Politechnika Poznańska | [ S ] student

Title variant

EN Principles of correct transformers measurements using SFRA method

Year of publication

2018

Published in

Poznan University of Technology Academic Journals. Electrical Engineering

Journal year: 2018 | Journal number: Issue 95

Article type

scientific article

Publication language

polish

Keywords
PL
  • SFRA
  • transformator energetyczny
  • funkcja przenoszenia
Abstract

PL W artykule zaprezentowano podstawowe zasady wykonywania pomiarów transformatorów energetycznych z wykorzystaniem metody SFRA. Przedstawiono sposoby podłączania przewodów pomiarowych, które zostały opisane w [1]. Zaprezentowano praktyczne aspekty pomiarów z uwzględnieniem dobrej praktyki pomiarowej, które pozwalają uzyskać wiarygodne i powtarzalne wyniki pomiarów, nadające się do porównywania z przebiegami wzorcowymi, uzyskanymi np. u producenta transformatora. Przeanalizowano wpływ sprzętu pomiarowego, sposobu podłączenia przewodów pomiarowych oraz innych czynników, które koniecznie należy uwzględnić podczas wykonywania pomiarów. Ponadto, autor przedstawił kilka przykładowych wyników błędnie wykonanych pomiarów, zrealizowanych na rzeczywistych transformatorach energetycznych o mocy 16 MVA oraz 630 kVA.

EN The article presents the basic principles of performing of SFRA measurements method on power transformers. Methods of connecting test leads are described, as shown in the standard [1]. Practical aspects of measurements, including good measurement practice, are presented, which allow to obtain reliable and reproducible measurement results, suitable for comparison with fingerprint waveform obtained, for example, from the manufacturer of transformer. The influence of measuring equipment, methods of connecting test leads and other factors, which must be taken into account during the measurements, are analyzed. Moreover, the author presented a few examples of incorrectly performed measurements, carried out on a real 16 MVA and 630 kVA power transformers.

Pages (from - to)

163 - 174

DOI

10.21008/j.1897-0737.2018.95.0016

Presented on

Computer Applications in Electrical Engineering 2018, 23-24.04.2018, Poznań, Polska

Full text of article

Download file

Access level to full text

public

Ministry points / journal

9

Ministry points / journal in years 2017-2021

9

This website uses cookies to remember the authenticated session of the user. For more information, read about Cookies and Privacy Policy.