Title

Porównanie przebiegów w systemie elektroenergetycznym w niesymetrycznych stanach pracy przy uwzględnieniu różnych modeli generatorów synchronicznych

Authors

Title variant

EN Comparison of the waveforms in a power system under asymmetric operating conditions when considering different synchronous generator models

Year of publication

2019

Published in

Poznan University of Technology Academic Journals. Electrical Engineering

Journal year: 2019 | Journal number: Issue 98

Article type

scientific article

Publication language

polish

Keywords
PL
  • system elektroenergetyczny
  • niesymetria obciążenia
  • zwarcie dwufazowe
  • modele generatora
  • asymetria podprzejściowa generatora
Abstract

PL W artykule porównano przebiegi wielkości wyjściowych różnych modeli matematycznych generatora synchronicznego pracującego w systemie elektroenergetycznym (SEE). Założono, że SEE składa się z zespołu wytwórczego (w skład którego wchodzi m.in. generator synchroniczny) połączonego linią przesyłową wysokiego napięcia z siecią sztywną. W przedstawionych wynikach obliczeń przyjęto zakłócenia stanu ustalonego w postaci zwarć symetrycznych i niesymetrycznych w wybranym miejscu linii przesyłowej. W modelu generatora uwzględniono m.in. asymetrię podprzejściową, która podczas zwarć niesymetrycznych powoduje występowanie wyższych harmonicznych w przebiegach prądów i napięć stojana oraz prądu wzbudzenia (także przy braku uwzględniania zjawiska nasycenia rdzeni magnetycznych generatora). Badano modele obwodowe generatora synchronicznego typu XT oraz RL przy przyjęciu różnych wielkości wejściowych i wyjściowych układu.

EN In the paper, the waveforms of the output quantities of different mathematical models of a synchronous generator operating in a power system (PS) are compared. It was assumed that the PS consisted of a generating unit (including, among others, the synchronous generator) connected by a high voltage transmission line to a bus. In the presented calculations results, disturbances of the steady state in the form of symmetric and asymmetric short-circuits in a selected place of the transmission line were assumed. In the generator model, the subtransient asymmetry which during asymmetric short-circuits results in occurrence of higher harmonics in the waveforms of stator currents and voltages as well as the field current (also when the phenomenon of magnetic saturation of the generator magnetic cores was not taken into account) were taken into account. The XT and RL circuit models of the synchronous generator when assuming different input and output quantities of the system were investigated.

Pages (from - to)

7 - 18

DOI

10.21008/j.1897-0737.2019.98.0001

Presented on

Computer Applications in Electrical Engineering 2019, 15.04.2019, Poznań, Polska

Full text of article

Download file

Access level to full text

public

Ministry points / journal

5

Ministry points / journal in years 2017-2021

5