Significance of SMES Devices for Power System Frequency Regulation Scheme Considering Distributed Energy Resources in a Deregulated Environment

Authors

[ 1 ] Instytut Elektroenergetyki, Wydział Inżynierii Środowiska i Energetyki, Politechnika Poznańska | [ P ] employee

Scientific discipline (Law 2.0)

[2.10] Environmental engineering, mining and energy

Year of publication

2022

Published in

Energies

Journal year: 2022 | Journal volume: vol. 15 | Journal number: iss. 5

Article type

scientific article

Publication language

english

Keywords
EN
  • automatic generation control
  • load frequency control
  • microgrid
  • power system deregulation
  • renewable generation
  • SMES
  • UPFC
Abstract

EN Nowadays, the restructuring of power systems is extremely urgent due to the depletion of fossil fuels on the one hand and the environmental impact on the other. In the restructured environment, the incorporation of renewable energy sources and storage devices is key as they have helped achieve a milestone in the form of microgrid technology. As the restructuring of the power system increases, there are several types of generation sources, and distribution companies express their interest in trading in a deregulated environment to operate economically. When considering the power system deregulation, the contract value deviates in some situations, resulting in an imbalance between the generation and the energy consumption, which can bring the system into a power outage condition. In particular, load frequency control has been a great challenge over the past few decades to ensure the stable operation of power systems. This study considers two generation sources: mini-hydro in GENCO-1 and 3 and microgrid (combination of wind, fuel cell, battery storage, and diesel engine) in GENCO-2 and 4. It is two equal-area networks; in area-1, GENCO-1 and 2, and in area-2, GENCO-3 and 4 are considered, respectively. In addition, a FOPID controller and two ancillary devices, such as a unified power flow controller and a superconducting magnetic energy storage system, have been incorporated. Three different test networks have been formed according to the contract value, such as unilateral, bilateral, and agreement violations. The simulation results show that ancillary devices and controller participation significantly enhance the system response by reducing the frequency and tie-line power fluctuation. To validate the efficacy of the proposed method, respective performance indices and percentages of improvement have been obtained. Finally, this study demonstrated the effectiveness of the proposed restructured power system in a deregulated environment.

Pages (from - to)

1766-1 - 1766-32

DOI

10.3390/en15051766

URL

https://www.mdpi.com/1996-1073/15/5/1766

Comments

article number: 1766

License type

CC BY (attribution alone)

Open Access Mode

open journal

Open Access Text Version

final published version

Date of Open Access to the publication

at the time of publication

Full text of article

Download file

Access level to full text

public

Ministry points / journal

140

Impact Factor

3,2

This website uses cookies to remember the authenticated session of the user. For more information, read about Cookies and Privacy Policy.