Depending on the amount of data to process, file generation may take longer.

If it takes too long to generate, you can limit the data by, for example, reducing the range of years.

Chapter

Download BibTeX

Title

Detection of intermittent earth faults in compensated MV network

Authors

[ 1 ] Instytut Elektroenergetyki, Wydział Elektryczny, Politechnika Poznańska | [ P ] employee

Year of publication

2003

Chapter type

paper

Publication language

english

Abstract

EN The experience acquired from the Polish medium voltage power distribution networks shows the unreliability of the localization criterions applied to the intermittent earth faults. It results from the lack of stability and low power level of the measuring signals falling often down below the protection's start-up level. In the paper, a new adaptive algorithm based on the wavelet analysis enabling detection of specific dynamics of the measuring signal during intermittent earth faults is presented. The algorithm was analyzed utilizing the signals generated in the EMTP program package.

DOI

10.1109/PTC.2003.1304614

URL

https://ieeexplore.ieee.org/document/1304614

Comments

Paper BPT03-76

Book

2003 IEEE Bologna PowerTech, June 23-26, 2003, Bologna, Italy : conference proceedings

Presented on

2003 IEEE Bologna PowerTech, 23-26.06.2003, Bologna, Italy