Depending on the amount of data to process, file generation may take longer.

If it takes too long to generate, you can limit the data by, for example, reducing the range of years.

Article

Download BibTeX

Title

Radiators Adjustment in Multi-Family Residential Buildings - An Analysis Based on Data from Heat Meters

Authors

[ 1 ] Instytut Inżynierii Środowiska i Instalacji Budowlanych, Wydział Inżynierii Środowiska i Energetyki, Politechnika Poznańska | [ P ] employee

Scientific discipline (Law 2.0)

[2.10] Environmental engineering, mining and energy

Year of publication

2023

Published in

Energies

Journal year: 2023 | Journal volume: vol. 16 | Journal number: iss. 22

Article type

scientific article

Publication language

english

Keywords
EN
  • heating
  • smart meters
  • TRV
  • occupant behavior
  • residential building thermostats
Abstract

EN Energy is consumed in buildings through the use of various types of energy systems, which are controlled by the occupants via provided interfaces. The quality of this control should be verified to improve the efficiency of the systems and for the comfort of the occupants. In the case of residential buildings, due to privacy reasons, it is problematic to directly monitor human–building interactions using sensors installed in dwellings. However, data from increasingly common smart meters are easily available. In this paper, the potential use of data from heat meters is explored for the analysis of occupant interactions with space-heating (SH) systems. A pilot study is conducted based on a one-year set of daily data from 101 dwellings. First, the identification of an indoor temperature and a strategy for thermostatic radiator valve (TRV) adjustments for all the investigated dwellings is presented. Second, the performed analysis suggests that 96% of the households did not use the automatic adjustment function of the TRVs since adjustments using the on–off mode were the most common, which could be empirical evidence for Kempton’s theory on mental models of home heating controls. The reasons for this could be the weakness of the TRV as an SH interface and the technical specificity of the analyzed SH (its supply temperature). The preliminary investigation confirms the potential of the proposed methodology, but further research is needed.

Date of online publication

08.11.2023

Pages (from - to)

7485-1 - 7485-22

DOI

10.3390/en16227485

URL

https://www.mdpi.com/1996-1073/16/22/7485

License type

CC BY (attribution alone)

Open Access Mode

open journal

Open Access Text Version

final published version

Date of Open Access to the publication

at the time of publication

Ministry points / journal

140

Impact Factor

3,2 [List 2022]