Depending on the amount of data to process, file generation may take longer.

If it takes too long to generate, you can limit the data by, for example, reducing the range of years.

Article

Download file Download BibTeX

Title

Thermal performance of multi-pipe earth-to-air heat exchangers considering the non-uniform distribution of air between parallel pipes

Authors

[ 1 ] Instytut Inżynierii Środowiska i Instalacji Budowlanych, Wydział Inżynierii Środowiska i Energetyki, Politechnika Poznańska | [ P ] employee

Scientific discipline (Law 2.0)

[2.10] Environmental engineering, mining and energy

Year of publication

2020

Published in

Geothermics

Journal year: 2020 | Journal volume: vol. 88

Article type

scientific article

Publication language

english

Keywords
EN
  • multi-pipe earth-to-air heat exchanger
  • airflow distribution
  • thermal performance
  • energy efficiency multi-tube
Abstract

EN In multi-pipe structures of earth-to-air heat exchangers (EAHEs), the airflow distribution between parallel pipes is not uniform and depends on many geometrical parameters, primarily the relation between the diameters of parallel pipes and manifolds, and the length of branch pipes. The phenomenon of airflow non-uniformity is usually neglected in the thermal performance calculations. This report investigates the influence of airflow distribution patterns on the thermal performance of multi-pipe EAHEs in order to bridge this knowledge gap. The calculations have been performed for a winter-time season for exchangers located in the climatic conditions of Central Europe. Analysis was conducted for different airflow conditions characterized by an airflow distribution uniformity coefficient. Results show that the thermal performance calculated for real EAHEs, with branch-pipes of a length L = 76d and diameters equal to the main pipe diameters, can be up to 28% lower than for ideal (uniform) distribution of air in an analogous exchanger. For EAHEs with branch-pipes of a length L = 300d and main pipes 1.4 times larger in diameter than parallel branch-pipes, the differences are much lower, i.e., less than 13%. The correlation between the airflow distribution uniformity coefficient and the EAHE seasonal heat gains is presented for exchangers consisting of 3, 5, 7, or 10 parallel branch-pipes. These results can be applied in various energy and economic analyses to estimate the potential energy savings from designing energy efficient building HVAC systems equipped with EAHEs characterized by better airflow distribution.

Pages (from - to)

101896-1 - 101896-11

DOI

10.1016/j.geothermics.2020.101896

URL

https://www.sciencedirect.com/science/article/pii/S0375650520301887?via%3Dihub

Comments

article number: 101896

License type

CC BY-NC-ND (attribution - noncommercial - no derivatives)

Open Access Mode

czasopismo hybrydowe

Open Access Text Version

final published version

Date of Open Access to the publication

at the time of publication

Full text of article

Download file

Access level to full text

public

Ministry points / journal

100

Ministry points / journal in years 2017-2021

100

Impact Factor

4,284