Impact of Cable Configuration on the Voltage Induced in Cable Screen during Work with One-Sidedly Ungrounded Cable Screen

Authors

[ 1 ] Instytut Elektroenergetyki, Wydział Inżynierii Środowiska i Energetyki, Politechnika Poznańska | [ P ] employee

Scientific discipline (Law 2.0)

[2.10] Environmental engineering, mining and energy

Year of publication

2021

Published in

Energies

Journal year: 2021 | Journal volume: vol. 14 | Journal number: no. 14

Article type

scientific article

Publication language

english

Keywords
EN
  • MV cable line
  • metallic cable screen
  • overvoltages
  • computer simulation
Abstract

EN In the latest research, it has been proven that from the point of view of losses in a cable distribution line, the most advantageous operation is to work with two or one phase of metallic cable screen ungrounded. However, such an operation may cause changes in the network characteristics and thus the occurrence of undesirable phenomena. One of those characteristics is the overvoltages in those cable screens, which can lead to cable line damage. The simulation tests presented in this article are closely related to the unusual method of operation of the MV cable screens and their performance, and they address the question of whether in a given system ground fault overvoltages may be a significant threat to the operation of the cable. The research methods used to verify these risks are related to the simulation of the cable line operating states using the DIgSILENT PowerFactory program (DIgSILENT GmbH, Gomaringen, Germany). Overvoltage simulations were performed, taking into account changes in the network configuration, such as the method of cable screens grounding, the length of cable lines, the cross-section of the conductor and cable screen, or the method of operation of the neutral point. The results for the cable line modeled as a part of the MV network with the variables considered during the tests indicate the possible impact of the one-sidedly cable screen ungrounding on overvoltages in this cable screen. The obtained results at the level of a few kV in one-sidedly ungrounded cable screens show that the change of the configuration of the operation of these cable screens may affect the safety of the network operation.

Pages (from - to)

4263-1 - 4263-14

DOI

10.3390/en14144263

URL

https://www.mdpi.com/1996-1073/14/14/4263

Comments

article number: 4263

License type

CC BY (attribution alone)

Open Access Mode

open journal

Open Access Text Version

final published version

Date of Open Access to the publication

at the time of publication

Ministry points / journal

140

Ministry points / journal in years 2017-2021

140

Impact Factor

3,252

This website uses cookies to remember the authenticated session of the user. For more information, read about Cookies and Privacy Policy.